Fan Selection by Airflow and Static Pressure
A fan’s maximum airflow and maximum pressure are usually reached at different operating points. Selecting from these two catalogue limits does not establish that the fan will perform the required duty. The starting point is the airflow and pressure that must be delivered together under stated air conditions.
State a complete duty point
Specify volumetric airflow, required pressure and the pressure definition. For example, 7200 m³/h at 400 Pa fan static pressure is an assumed duty used only for explanation. It is neither a performance claim for a Voltvent product nor a recommendation for a particular installation.
State whether airflow is actual volume at operating conditions or a value converted to reference conditions. Temperature and altitude affect density. Curves must identify density, speed and configuration before selections can be compared on a consistent basis.
Distinguish static pressure from total pressure
At a measurement section, total pressure is the sum of static and velocity pressure: pₜ = pₛ + pᵥ. Fan total pressure is the difference between outlet and inlet total pressures. Fan static pressure should not simply be treated as the difference between two static readings; check the rating definition and connection arrangement.
For a unit example, 7200 m³/h = 2 m³/s. With a net section area A = 0.5 m², mean velocity v = Q/A = 4 m/s. Assuming ρ = 1.2 kg/m³ only for this example gives pᵥ = ρv²/2 = 9.6 Pa. This section calculation is not an extra loss to add automatically to the 400 Pa duty. Define the boundaries and sections before converting pressure values.
Build a pressure budget at the design airflow
Assess duct friction, fittings, branches, transitions, filters, coils, dampers, silencers and terminals along the relevant air path. Do not add the losses of parallel branches indiscriminately; consider network balance and the critical path. Keep pressure definitions consistent and avoid counting any component twice.
Check the duties for clean and expected loaded filters separately. An elbow close to the inlet, restricted entry or an unsuitable discharge connection can introduce system effects. Account for differences between the laboratory test arrangement and the installation.
Read the fan and system curves together
At a fixed speed and defined system conditions, the operating point lies where the fan curve intersects the system curve. Damper position, filter loading and speed changes can move this point. Assess the expected operating range and stable region as well as the design point.
Do not choose a fan type from its name alone. Axial, centrifugal and duct arrangements must be assessed against pressure, air properties, available space and the selected model curve. Repeated, unjustified allowances can lead to oversizing, noise and inefficient operation.
Compare proposals on the same basis
Compare efficiency, speed and power at the specified point. Shaft power, motor rated power and electrical input power are different quantities. State whether drive and controller losses are included. Sound power and sound pressure are also different; compare the same quantity under stated conditions.
The selection record should include the curve, air density, control range, dimensions and service access. For fire smoke or explosive atmosphere duties, check the specific documentation and limits separately. At commissioning, verify airflow, pressure, electrical readings and control operation. A model code alone is not evidence of installed system performance.
Send Voltvent the airflow, pressure definition, air conditions and duct arrangement together for a technical selection review.